Overhead Feeder Switching
Switching 11, 22 and 33 kV overhead feeders under load, for maintenance, load transfer and fault isolation.
Switchgear
Premium, state of the art outdoor and indoor load break switches for 11 to 33 kV networks, including 60 Hz 13.8 and 34.5 kV systems, rated 12 to 38.5 kV and 400 to 1,250 A.
Pole mounted switches quench the arc in oil or vacuum, and indoor switches combine with high voltage fuses for transformer protection, including 60 Hz air insulated panel switches with no oil or gas. Most switches are also disconnectors, so one device switches load current and provides safe isolation.

Our load break switches are switch disconnectors to IEC 62271-103: they make and break load current and, when open, provide the isolating distance of a disconnector. Switch fuse combinations are to IEC 62271-105.
Pole and structure mounted three pole switches rated 12, 24, 36 and 38.5 kV and 400 or 630 A, with the arc quenched in oil filled chambers. Available in two designs.
Pole and structure mounted three pole switches rated 12, 24, 36 and 38.5 kV and 400, 630 or 1,250 A, with vacuum interrupters and no oil.
Multipurpose switch disconnectors rated 400, 630 or 1,250 A for indoor switchboards and substations, also supplied as switch fuse combinations.
Switch disconnectors rated 400, 630 or 1,250 A, with several switch fuse arrangements for transformer and feeder circuits.
Switch disconnectors rated up to 400 A for transformer feeders, combined with high voltage fuses.
Premium, state of the art panel mounted three pole switches rated 24 kV and 630 A at 60 Hz, for 60 Hz networks such as those in the North Pacific, and built to the highest IEC electrical endurance class, E3. An air puffer blows out the arc as the contacts open, with no oil or gas. Fuse versions take current limiting fuses up to 100 A, where many comparable switches stop at 63 A, carry a 1,250 A transfer current, and trip all three phases if one fuse blows, so a transformer never runs on two phases. Operated from the panel door by cable or by motor, with a shunt trip for protection relays.
Fuse links rated 7.2 to 40.5 kV and up to 160 A for indoor and outdoor use, with striker pin, optional thermal protection, and versions suitable for SF6 switchgear.
Single, double and triple hand actuators, or a motor drive for remote switching and network automation.
Typical ratings for the standard range. Final values are confirmed for each project.
Customised designs available. If your project needs ratings, features, design requirements or arrangements outside the standard range below, we design and manufacture to your requirements and application.
| Parameter | Standard | Optional or on request |
|---|---|---|
| Switch types | Outdoor three pole load break switches; indoor switch disconnectors; indoor air insulated load break switches; switch fuse combinations | Customer specific multipole switches |
| Arc quenching, outdoor switches | Oil or vacuum | |
| Rated voltage | IEC: 12, 24, 36 and 38.5 kV, 50 Hz IEEE/ANSI: 15.5, 27 and 38 kV, 60 Hz | |
| Rated current | ||
| Outdoor, oil | 400 A, 630 A | |
| Outdoor, vacuum | 400 A, 630 A, 1,250 A | |
| Indoor, 12 to 38.5 kV | 400 A, 630 A, 1,250 A | |
| Indoor, 12 and 24 kV | 400 A, 630 A, 1,250 A | |
| Transformer switch disconnector, 24 kV | Up to 400 A | |
| Indoor air insulated, 24 kV | 630 A | Fuse versions with fuses up to 100 A |
| Indoor air insulated load break switches, 24 kV | ||
| Rated frequency | 60 Hz | |
| Switch class | E3 electrical, M1 mechanical (IEC 62271-103) | |
| Short time withstand current | 20 kA for 1 second | |
| Making current | 52 kA peak | 104 kA peak with fuses |
| Breaking current with fuses | 40 kA | |
| Transfer current | 1,250 A (fuse versions) | |
| Lightning impulse withstand | 125 kV to earth; 145 kV across the open gap | |
| Power frequency withstand | 50 kV to earth; 60 kV across the open gap | |
| Switching duty | 100 operations at 630 A; 20 loop switching operations; cable and line charging; 1,000 no load operations | |
| Operation | Manual from the panel door by flexible cable | Motor operation, 110 V DC or 110 and 220 V AC; shunt trip; auxiliary contacts |
| Fuse protection | Trips all three phases if one fuse blows; blown fuse indication contact | |
| Ambient conditions | Up to +40°C; altitude up to 1,000 m | |
| High voltage HRC fuses | ||
| Rated voltage | 7.2, 12, 24, 36 and 40.5 kV | |
| Rated current | Up to 160 A | |
| Features | Striker pin; indoor and outdoor versions | Thermal protection; versions for SF6 switchgear |
| Operation | Hand actuators, single, double or triple | Motor drive |
| Standards | IEC 62271-103; IEC 62271-105; fuses to IEC 60282-1 | |
Premium, state of the art switches engineered for reliable load switching and safe isolation, outdoors and indoors.
Each switch makes and breaks load current and, when open, provides the isolating distance of a disconnector, so a separate isolator is not needed.
Outdoor switches are available with oil filled arc quenching chambers or with vacuum interrupters and no oil, so the choice can follow network practice and maintenance preference.
Switch fuse combinations protect distribution transformers with high voltage HRC fuses, and striker pins signal a blown fuse.
Outdoor switches take a motor drive for remote switching from a control room or automation scheme, alongside manual hand actuators.
Multipole and customer specific switch arrangements are available on request.
The indoor air insulated switches meet the highest IEC electrical endurance class, E3, with a spring operating mechanism built for long service life. Fuse versions protect transformers up to about 2.6 MVA with fuses up to 100 A, and a mechanical fuse trip opens all three phases when a single fuse blows.
Delstar supplies load break switches for:
Switching 11, 22 and 33 kV overhead feeders under load, for maintenance, load transfer and fault isolation.
Motorised switches for remote switching and feeder automation schemes.
Switching and isolating transformers on overhead networks.
Switch disconnectors and switch fuse combinations for MV switchboards in substations, kiosks and plant rooms.
MV distribution on mine sites, plants and private networks.
Switching points where solar farms and other generation connect to the network.
Our load break switches are premium products from established manufacturers. The outdoor and European indoor ranges are made by a switchgear maker with over a century of experience, and the 60 Hz air insulated switches by an established Asian manufacturer of medium and high voltage switchgear whose group builds equipment to nuclear power plant quality standards. All are type tested to IEC 62271-103, with switch fuse combinations to IEC 62271-105. Delstar delivers to site across New Zealand, Australia and the Pacific.
Talk to our team
Send us your network voltage, rated current, fault level, indoor or outdoor installation and site conditions, and we will recommend the right switch and confirm availability, lead time and local support.