Laboratory Calibration Benches
Multi position benches for calibrating and verifying meters in volume.
| Parameter | Standard |
|---|---|
| Configuration | |
| Test positions | 10, 20 or 40 meters at a time in a modular rack, other sizes on request |
| Meter types | Single phase and three phase (3 and 4 wire), static and electromechanical, active and reactive energy |
| Meter connection | Universal quick connection for IEC and BS meters, ANSI S type sockets available |
| Supply | 3 x 230/400 V three phase as standard, other supply voltages on request |
| Reference standard | |
| Accuracy | Class 0.01 or 0.02, four quadrant, active, reactive and apparent energy |
| Method | Energy comparison against a three phase reference standard |
| Measuring range | 30 to 320 V, 1 mA to 120 A, 45 to 65 Hz |
| Test chain | Complete chain of contacts, wiring, error calculators and scanning heads certified by an accredited laboratory |
| Voltage and current generation | |
| Voltage | 30 to 320 V per phase, 600 VA per phase, with a 480 V option for ANSI meters on 277/480 V networks, higher powers on request |
| Current | 1 mA to 120 A per phase, 1200 VA per phase, 200 A on request |
| Phase angle | Adjustable from minus 180 to plus 180 degrees, 0.01 degree resolution, balanced and unbalanced |
| Frequency | 45 to 65 Hz |
| Stability and distortion | Output stability better than 0.05%, total harmonic distortion under 0.3% |
| Harmonics | 2nd to 13th harmonic as an option |
| Tests | |
| Standard tests | Pre warming, creep and starting, no load, adjustment and calibration, accuracy and dial (register) |
| Optional tests | Harmonic, and voltage interruption and dip, with tamper tests configurable |
| Features | |
| Closed link testing | Isolation current transformers test meters with the current link closed |
| Bypass | Electronic monitored bypass, including hot bypass for prepaid meters that open their circuit |
| Predictive maintenance | Contact impedance monitored for every position before testing |
| Scanning heads | Optical heads for disc marks, LED, LCD and infrared pulses, with automatic adjustment |
| Error calculators | Touch screen calculator at each row of positions |
| Handheld terminal | Barcode reader linked wirelessly to the control software |
| Safety | Warning beacon and two emergency stops |
| Standards | |
| Test equipment | IEC 62057-1 stationary meter test units, IEC 61010-1 safety |
| Meters tested to | IEC 62052-11, IEC 62053-21, 62053-22 and 62053-23, IEC 62058-11, 62058-21 and 62058-31, EN 50470-3, ANSI C12.1 |