Three Phase Meters
One three phase meter platform for prepaid, postpaid and smart metering, in the same way as the single phase range. It is built as direct connected, CT connected or CT/VT connected meters, for homes, commercial sites and large industrial customers. Prepaid with STS 6 tokens, postpaid, or smart with communications built in. Prepaid and postpaid meters can be supplied without communications and have plug in G3-PLC, BPLC, Wi-SUN, LoRaWAN or cellular modules, including NB-IoT and LTE-M, fitted at installation or added later. Accuracy is class 1.0, with class 0.5S and 0.2S available, and a polyphase keypad version adds power quality measurement to the 50th harmonic.
| Prepaid | STS6 compliant. Pay in advance, with credit loaded by token or remotely |
|---|---|
| Postpaid | Conventional billing, no communications. Communications can be added later |
| Smart | Prepaid or postpaid with communications built in |
| Connection | Direct connected, CT connected or CT/VT connected |
|---|---|
| Reference voltage | 3 x 230/400 V or 3 x 240/415 V |
| Current | Direct connected: 5 (100) A CT and CT/VT connected: to suit the instrument transformers |
| Accuracy | Class 1.0 kWh; class 2.0 kvarh Optional: Class 0.5S or 0.2S kWh |
| Frequency | 50 Hz, ±5% Optional: 50 or 60 Hz, ±2% |
| Measurement | Four quadrant, three phase |
| Operating voltage range | 70% to 130% of reference voltage |
| Impulse voltage withstand | Rated 6 kV impulse and 6 kV lightning surge Tested beyond the IEC 62052-11 requirement |
| AC voltage withstand | 4 kV |
| Fast transient burst immunity | 4 kV |
| Electrostatic discharge | Contact 8 kV, air 15 kV |
| Tariffs | Up to 8 tariffs, 6 seasons, 100 special days |
| Token entry | Remote credit transfer Optional: 20 digit STS 6 tokens by keypad |
| Load switch | None Optional: Bi-stable relay, to 100 A (direct connected only) |
| Communications | Plug in module, fitted at installation or retrofitted later Optional: Embedded G3-PLC (smart version) |
| WAN communications | Plug in module Optional: G3-PLC, BPLC, Wi-SUN RF mesh, LoRaWAN, GPRS, 3G, 4G, NB-IoT, LTE-M |
| Event logging | Tamper, failure and power quality events |
| Data security | DLMS/COSEM with low level and high level security Optional: Security Suite 1 |
| Power quality | Under and over voltage (sag and swell), current imbalance and over current events logged Optional: Harmonic measurement to the 50th (polyphase keypad version) |
| Standards | IEC 62052-11; IEC 62053-21 and 62053-23; EN 50470-1 and 50470-3 (European MID); IEC 62055-31 for prepaid |
| Certification | SGS certified; MID certified to EN 50470 with KEMA certification; type tested to IEC and European standards |
| Firmware upgrade | Local interface and over the air |
| Protection | IP54; Class II insulation |
| Operating temperature | −25°C to +55°C Optional: −40°C to +70°C limit range |
| Humidity | Up to 95%, non-condensing |
| Design life | 15 years or more |